Portable Three Phase Reference Standard Meter MCSB03B
Mains Supple dolor | 45-450V, 45-65Hz |
Potentia consummatio | Max 20VA |
Influence ab externa potentia copia in test effectus | ≤0.005% cum mutatione X% |
Operatio Temperature | -10 °F .+50°C |
Temp.Co efficientiam | ≤0.0025%/ °C +10°C ad +40°C≤0.0050%/°C -10°C ad +50°C |
Frequency range | 45…70Hz |
Influentia ab externo magnetico agro | ≤0.07 % /0.5mT |
Tempus turpis | 1-99s |
Current Test | |
Recta modusRange:1mA-120APropono solutionem: 6 numeri validi Error mensurae: ≤ ± 0.02% 10mA…120A ≤ 0.02% ad 0.05% 1mA ad 10mA | Fibulae modusRange: 10A, 50A, 100A, 300A,500A,1000A, 3000A (libitum)Propono solutionem: 6 numeri validi Error mensurae: ≤0.2% |
Voltage Test | |
Range | 1V….560V |
Propono resolutio | VI valida numeri |
Error mensurae | ≤± 0.02% (30V…560V) |
Onus Mensurae | |
Voltage range | 0V…5V |
Propono range | 0.000mv…5.000v |
Error mensurae | ≤ ± 1.0% |
Vis mensurae (active, reactivum, apparent) | |||
Error: ≤0.02% 40V~576V,10mA~120A,PF≥0.5, 2-21 Tempora harmonica Wave) | |||
DC mensurae | |||
Range | 0 ± 20 mA | 0V …± 10V | |
error | E <± 1.0% | E <± 1.0% | |
Propono range | 0.00 mA…20.00 mA | 0.000V….10.000V | |
Energy mensurae error | |||
Active & apparent: 0.02% (modus directus) & 0.2% (fibulae modus)Reactivum: 0.04% (modus directus) & 0.4% (fibulationis modus) | |||
Potentia factor measurement | |||
Error | E ≤± 0.0002 | ||
Propono range | -1.00000….+ 1.00000 | ||
Resolution | 0.011 | ||
Frequentia mensurae | |||
Error | ±0.005% RD | ||
Range | 40-70HZ | ||
Propono range | 40.0000HZ ad 69.9990HZ | ||
Harmonic contentus measurement | |||
Tempora | 2 - 51times | ||
Error | ±10% RD±0.1% |
Epistulam tuam hic scribe et mitte nobis